APlus M33-LV 60K ~ 140KVA

Offering high efficiency and overload capacity, APlus M33-LV is a truly modular UPS system which can easily scales in 30KW increments up to 140KW. Modular design is applied in power module, STS module and battery module. It will simplify maintenance and replacement with low MTTR.

  Main Features
  • High efficiency online double conversion technology
  • High scalability
  • Unity output power factor
  • Modular design lowers MTTR
  • N+1 or N+X parallel redundancy for power guarantee
  • Ease of installation and maintenance
  • Flexible battery configuration adapts different applications
  • Highly reliable operation with redundant power supply in STS
  • User-adjustable charging current
  • High overload capability



  MODELM33-LV20-60KM33-LV20-80KM33-LV20-80KLM33-LV20-120KLM33-LV20-140KL
  PHASE3-phase in / 3-phase out
  CABINET CAPACITY*60 KW80 KW80 KW120 KW140 KW
  BATTERY TYPEBuilt-in BatteryExternal Battery
  ONE POWER MODULE CAPACITY20KVA/20KW
  MAX. POWER MODULE NO.34467+1
  MAX. BATTERY SET NO.**34---
  INPUT
  Nominal Voltage3 x 208/220 VAC (3Ph+N)
  Voltage Range182V ~ 253V at 90% ~100% load
156V ~ 253V at 63% ~90% load 121V ~ 253V for <63% Load
  Nominal Frequency50/60Hz (Auto sensing)
  Frequency Range40Hz ~70Hz
  Power Factor> 0.99 at 100% load, >0.98 at 50% load
  Harmonic Distortion (THDi)< 3% @ 100% load
  OUTPUT
  Nominal Voltage3 x 208V/220VAC (3Ph+N)
  Voltage Regulation (Steady state) ± 1% Typical (balanced load) ;   ± 2% Typical (imbalanced load)
  Nominal Frequency50/60Hz
  Frequency Range (Synchronized)46Hz ~ 54Hz or 56Hz ~ 64Hz
  Overload Capability1 hour for 110%, 10 mins for 125%,; 1 min for 150%, 200ms for >150%
  Harmonic Distortion 2% THD (Linear Load) ;  4% THD (Non-linear Load)
  EfficiencyUp to 92.5% at over 50% load
  BATTERY / CHARGER
  Nominal Voltage+/- 120V (12V x 20 pcs)
  Float Charging Voltage2.3V / Cell
  Boost Charging Voltage2.35V / Cell
  Temperature CompensationYes
  Maximum Charging Current8A for each power module (User-adjustable)
  PHYSICAL
  Cabinet Dimension (D x W x H) mm1100 x 600 x 14751100 x 600 x 20101100 x 600 x 14751100 x 600 x 14751100 x 600 x 2010
  Net Weight (kg)670.5926329428.57 Power Modules: 504
8 Power Modules: 537
  ENVIRONMENT
  Operating Temperature0 ~ 40°C
  Relative Humidity0 ~ 95% non-condensing
  Altitude<1000m for Nominal power
  IP ProtectionIP 20
  MANAGEMENT
  Smart RS-232 / USBSupports Windows® Family, Linux and MAC
  Optional SNMPPower management from SNMP manager and web browser
  STANDARDS
  SafetyUL1778, CSA C22.2 No. 107.3-05
  EMCFCC Part 15,Subpart B Class A


       *    When temperature is above 30, the output power factor will be de-rated, 0.9 at 31~35 and 0.8 at 36~40.

       **  One battery module contains 10 pcs of 12V/7Ah or 12/9Ah sealed lead acid batteries in one tray. One complete battery set contains 4 battery modules. 

       *** If the UPS is installed or used in a placewhere the altitude is above than 1000m, the output power must be derated one percent per 100m.


  ModelDescriptionDimension DxWxH(mm)Weight (kg)
  PM-20K-LV3P/3P 20KVA / 20KW Power Module736.5 x 490 x 133 (3U)34.5
  Battery Module10 PCS of 12V 9Ah Batteries710 x 107 x 15426


APlus M33-LV 60K ~ 140KVA
Offering high efficiency and overload capacity, APlus M33-LV is a truly modular UPS system which can easily scales in 30KW increments up to 140KW. Modular design is applied in power module, STS module and battery module. It will simplify maintenance and replacement with low MTTR.
Long press to look detail
Long by picture save/share

APlus M33-LV 60K ~ 140KVA

INQUIRY

enquiry form:

  • Please enter the verification code

enquiry content:


You have no items to require

Copyright @ 2021 Honyis Power Solutions Co., Ltd. All Rights Reserved

 

 粤公网安备 44030702003778号      ICP备2021024839号-1

let's chat now
添加微信好友,详细了解产品
使用企业微信
“扫一扫”加入群聊
复制成功
添加微信好友,详细了解产品
我知道了
粤ICP备2021024839号-1