Galleon R11-1U is designed with Slim 1U form factor, perfect to fit for data processing and transmission such as servers, networking and IP telephone services. it provides clean, high level quality power to fully protect mission-critical devices.
Main Features |
|
|
|
|
|
|
|
|
MODEL | R11-1U-1K | R11-1U-1KL | |
CAPACITY | 1000 VA / 800 W | 1000 VA / 800 W | |
INPUT | |||
Voltage | 110/120 VAC or 220/230/240 VAC | 220/230/240 VAC | |
Acceptable Voltage Range | 55-150 VAC or 110-300 VAC @ 50% load 80-150 VAC or 160-300 VAC @ 100% load | 110-300 VAC @ 50% load 160-300 VAC @ 100% load | |
Frequency Range | 40-70 Hz | ||
Power Factor | ≧ 0.99 @ Nominal voltage (full load) | ||
OUTPUT | |||
Output Voltage | 110/120 VAC or 220/230/240 VAC | 220/230/240 VAC | |
Voltage Regulation | ± 1% | ||
Frequency Range (Synchronized Range) | 57 ~ 63 Hz or 47 ~ 53 Hz | ||
Frequency Range (Battery. Mode) | 60 Hz or 50 Hz ± 0.3 Hz | ||
Current Crest Ratio | 5:1 (110/120 VAC) 3:1 (220/230/240 VAC) | 3:1 | |
Harmonic Distortion | ≦ 3 % THD (Linear Load) ≦ 5 % THD (Non-linear Load) | ||
Transfer Time | AC Mode to Battery Mode | 0ms | |
Inverter to Bypass | 4 ms (Typical) | ||
Waveform (Battery Mode) | Pure Sine Wave | ||
EFFICIENCY | |||
AC Mode | 86% | ||
ECO Mode | 92% | ||
Battery Mode | 83% | ||
BATTERY | |||
Battery Type | Lithium-iron battery or Sealed Lead-acid battery | Lithium-iron battery or Sealed Lead-acid battery | |
Battery Voltage | 24 VDC | 48 VDC | |
Battery Spec & Numbers | 6 V / 9 Ah x 4 | Depending on external battery capacity | |
Typical Recharge Time | 9 hours recover to 90% capacity | ||
Charging Current | 1A | 6A | |
INDICATORS | |||
LED | AC mode, Battery mode, and fault indicators | ||
ALARM | |||
Battery Mode | Sounding every 4 seconds | ||
Low Battery | Sounding every second | ||
Overload | Sounding twice every second | ||
Fault | Continously sounding | ||
PHYSICAL | |||
Dimension, (mm) DxWxH | 477 x 438 x 44 | 300 x 438 x 44 | |
Net Weight (kgs) | 12.6 | 6 | |
ENVIRONMENT | |||
Humidity | 20-90 % RH @ 0- 50°C (non-condensing) | 20-90 % RH @ 0-55°C (non-condensing) | |
Noise Level | Less than 50dB @ 1 Meter | ||
MANAGEMENT | |||
USB or RS-232 | Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7/8/10, Linux and MAC | ||
Dry Contact (Option) | Signal for AC Power Normal, Battery OK and Fault Alarm |