Galleon R22-LV 6KVA / 10KVA

  Main Features
  • True double-conversion 
  • DSP technology guarantees high performance
  • Output power factor 0.8 
  • Wide input voltage range (60-150 VAC)
  • Active input power factor correction 0.99
  • 50Hz/60Hz frequency converter mode
  • ECO mode operation for energy saving (ECO) 
  • Emergency power off function (EPO)
  • Generator compatible 
  • Charger capacity expansion to 8A for long-run models
  • SNMP/USB/RS-232 communications
  • 3-stage extendable charging design for optimized battery performance
  • Maintenance bypass available
  • Adjustable battery numbers






  MODELR22-LV-6K(L)R22-LV-10K(L)
  PHASE2-phase in / 2-phase out
  CAPACITY6000 VA / 4800 W10000 VA / 8000 W
  INPUT
  Nominal Voltage100/110/115/120/127 VAC (L-N)
  Voltage Range60-150 VAC (Ph-N) at 50% load ; 80-140 VAC (Ph-N) at 100% load
  Frequency Range46~54 Hz or 56~64 Hz
  Phase Angle0°/120°/180°/240°
  Power Factor≧0.99  @ 100% Load
  OUTPUT
  Output Voltage100/110/115/120/127 VAC (L-N)
  Phase Angle0°/120°/180°/240°
  AC Voltage Regulation (Batt. Mode)± 1%
  Frequency Range (Synchronized Range)46~54 Hz or 56~64 Hz
  Frequency Range (Batt. Mode)50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz
  Current Crest Ratio3:1 (max.)
  Harmonic Distortion≦ 2 % THD (Linear Load), ≦ 5 % THD (Non-linear Load)
  Transfer Time  AC Mode to Battery ModeZero
  Inverter to BypassZero
  Inverter to ECO< 10ms
  Waveform (Batt. Mode)Pure Sinewave
  EFFICIENCY
  AC Mode90.5%91%
  ECO Mode96%96%
  Battery Mode87%88%
  BATTERY
  Standard Model  Battery Type12 V / 7 Ah12 V / 9 Ah
  Numbers10 pcs x 2 strings10 pcs x 2 strings
  Typical Recharge Time5 hours recover to 90% capacity7 hours recover to 90% capacity
  Charging Current (max.)2.0 A2.0 A
  Float Charging Voltage136.5 VDC
  Long-run Model  Battery TypeDepending on applications
  Numbers
  Charging Current (max.)8.0 A
  Float Charging Voltage136.5 VDC
  INDICATORS
  LCD DisplayUPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions
  ALARM
  Battery ModeSounding every 4 seconds
  Low BatterySounding every second
  OverloadSounding twice every second
  FaultContinously sounding
  PHYSICAL
  Standard Model  Dimension, D x W x H(mm)

UPS Unit : 668 x 438 x 133 [3U]

Battery Pack : 580 x 438 x 133 [3U]

UPS Unit : 668 x 438 x 266 [6U]

Battery Pack : 580 x 438 x 133 [3U]

  Net Weight (kgs)

UPS Unit : 22

Battery Pack : 63

UPS Unit : 45

Battery Pack : 63

  Long-run Model  Dimension, D x W x H(mm)668 x 438 x 133 [3U]668 x 438 x 266 [6U]
  Net Weight (kgs)2245
  ENVIRONMENT
  Operation Humidity0-95 % RH @ 0- 40°C (Non-condensing)
  Noise LevelLess than 60dB @ 1 Meter
  MANAGEMENT
  Smart RS-232 / USBSupports Windows2  2000/2003/XP/Vista/2008, Windows2  7/8, Linux and MAC
  Optional SNMPPower management from SNMP manager and web browser


      *    Derate Capacity to 60% of capacity in CVCF mode and to 90% when the output voltage is adjusted to 100VAC. 

        **  If the UPS is installed or used in a place where the altitude is above than 1000m, the output power must be derated one percent per 100m.


DatasheetGalleon R22-LV_Datasheet
User ManualComing soon


Galleon R22-LV 6KVA / 10KVA
Long press to look detail
Long by picture save/share

Galleon R22-LV 6KVA / 10KVA

INQUIRY

enquiry form:

  • Please enter the verification code

enquiry content:


You have no items to require

Copyright @ 2021 Honyis Power Solutions Co., Ltd. All Rights Reserved

 

 粤公网安备 44030702003778号      ICP备2021024839号-1

let's chat now
添加微信好友,详细了解产品
使用企业微信
“扫一扫”加入群聊
复制成功
添加微信好友,详细了解产品
我知道了
粤ICP备2021024839号-1