APlus M33-30 90KVA ~ 300KVA

Offering high efficiency and overload capability, APlus M33-30 is truly modular UPS system which can easily scales in 30KW increments up to 300KW. Modular design is applied in power module, STS module and battery module. It will simplify maintenance and replacement with low MTTR.

  Main Features
  • High efficiency online double conversion technology
  • High scalability
  • Unity output power factor
  • Modular design lowers MTTR
  • N+1 or N+X parallel redundancy for power guarantee
  • Ease of installation and maintenance
  • Flexible battery configuration adapts different applications
  • Highly reliable operation with redundant power supply in STS
  • User-adjustable charging current
  • High overload capability
  • Graphic 5.7”LCD design for easy management
  • Optional 10" touch LCD panel


  MODEL M33-30-90K M33-30-120K M33-30-90KL M33-30-120KL M33-30-180KL M33-30-210KL M33-30-300KL
  PHASE 3-phase in / 3-phase out
  CABINET CAPACITY* 90 KW 120 KW 90KW 120 KW 180 KW 210 K 300 KW
  BATTERY TYPE Built-in Battery External Battery
  ONE POWER MODULE CAPACITY 30KVA / 30KW
  MAX. POWER MODULE NUMBER 3 4 3 4 6 8 10
  MAX. BATTERY SET NUMBER** 3 5 - - - - -
  INPUT
  Nominal Voltage 3 x 380VAC/400VAC/415VAC (3Ph+N)
  Voltage Range 305 ~ 478 VAC at 100% load; 208 ~ 478VAC at <70% load
  Nominal Frequency 50/60Hz (Auto Sensing)
  Frequency Range 40Hz ~70Hz
  Power Factor > 0.99 @ 100% Load , >0.98 @ 50% Load
  Harmonic Distortion (THDi) < 3% @ 100% load
  OUTPUT
  Nominal Voltage 3 x 380VAC/400VAC/415VAC (3Ph+N)
  Voltage Regulation (Steady state) ≦± 1% Typical (balanced load) ; ≦  ± 2% Typical (imbalanced load)
  Nominal Frequency 50/60Hz
  Frequency Range (Synchronized) 46Hz ~ 54Hz or 56Hz ~ 64Hz
  Overload Capability 1 hour for 110%, 10 mins for 125%,; 1 min for 150%, 200ms for >150%
  Harmonic Distortion ≦  2% THD (Linear Load) ; ≦ 4% THD (Non-linear Load)
  Efficiency Up to 94.5%
  BATTERY / CHARGER
  Nominal Voltage +/- 216V (12V x 36 pcs)
  Maximum Voltage +/- 240V (12V x 40 pcs)
  Minimum Voltage +/- 192V (12V x 32 pcs)
  Float Charging Voltage 2.25V / Cell
  Boost Charging Voltage 2.35V / Cell
  Temperature Compensation Yes

  Maximum Charging Current 

  (Per Power Module)

8A
  PHYSICAL
  Cabinet Dimension (D x W x H) mm 1100 x 600 x 1475 1100 x 600 x 2010 1000 x 515 x 736 1100 x 600 x 1475 1100 x 600 x 2010
  Net Weight  (Kg) 675 932 183.5 335 437.5 549 620
  ENVIRONMENT
  Operating Temperature 0 ~ 40°C
  Relative Humidity 0 ~ 95% non-condensing
  Altitude <1000m for Nominal power
  IP Protection IP 20
  MANAGEMENT
  Smart RS-232 / USB Supports Windows® Family, Linux and MAC
  Optional SNMP Power management from SNMP manager and web browser
  STANDARDS
  Safety IEC/EN 60950-1; IEC/EN 62040-1
  EMC IEC/EN 62040-2 Category C3


  Model Description Dimension DxWxH(mm) Weight (kg)
  PM-30 3P/3P 30KVA/30KW Power Module 750 x 438 x 130 (3U) 34.5
  Battery Module 10 PCS of 12V 9Ah Batteries 710 x 107 x 154 26


APlus M33-30 90KVA ~ 300KVA
Offering high efficiency and overload capability, APlus M33-30 is truly modular UPS system which can easily scales in 30KW increments up to 300KW. Modular design is applied in power module, STS module and battery module. It will simplify maintenance and replacement with low MTTR.
Long press to look detail
Long by picture save/share
INQUIRY

enquiry form:

  • Please enter the verification code

enquiry content:


You have no items to require

Add Successfully

APlus M33-30 90KVA ~ 300KVA

Enquiry
INQUIRY

enquiry form:

  • Please enter the verification code

enquiry content:


You have no items to require

Add Successfully

Copyright @ 2021 Honyis Power Solutions Co., Ltd. All Rights Reserved

 

 粤公网安备 44030702003778号      ICP备2021024839号-1

Copyright @ 2022 

Honyis Power Solutions Co., Ltd.

All Rights Reserved

 

 粤公网安备 44030702003778号      

ICP备2021024839号-1

 

let's chat now
添加微信好友,详细了解产品
使用企业微信
“扫一扫”加入群聊
复制成功
添加微信好友,详细了解产品
我知道了
粤ICP备2021024839号-1