Offering high efficiency and overload capacity, APlus M33-LV is a truly modular UPS system which can easily scales in 20KW increments up to 140KW. Modular design is applied in power module, STS module and battery module. It will simplify maintenance and replacement with low MTTR.
Main Features |
|
|
|
|
|
|
|
|
|
|
MODEL | M33-LV20-60K | M33-LV20-80K | M33-LV20-80KL | M33-LV20-120KL | M33-LV20-140KL | |
PHASE | 3-phase in / 3-phase out | |||||
CABINET CAPACITY* | 60 KW | 80 KW | 80 KW | 120 KW | 140 KW | |
BATTERY TYPE | Built-in Battery | External Battery | ||||
ONE POWER MODULE CAPACITY | 20KVA/20KW | |||||
MAX. POWER MODULE NUMBER | 3 | 4 | 4 | 6 | 7+1 | |
MAX. BATTERY SET NUMBER** | 3 | 4 | - | - | - | |
INPUT | ||||||
Nominal Voltage | 3 x 208/220 VAC (3Ph+N) | |||||
Voltage Range | 182V ~ 253V at 90% ~100% load 156V ~ 253V at 63% ~90% load 121V ~ 253V for <63% Load | |||||
Nominal Frequency | 50/60Hz (Auto sensing) | |||||
Frequency Range | 40Hz ~70Hz | |||||
Power Factor | > 0.99 at 100% load, >0.98 at 50% load | |||||
Harmonic Distortion (THDi) | < 3% @ 100% load | |||||
OUTPUT | ||||||
Nominal Voltage | 3 x 208V/220VAC (3Ph+N) | |||||
Voltage Regulation (Steady state) | ≦ ± 1% Typical (balanced load) ; ≦ ± 2% Typical (imbalanced load) | |||||
Nominal Frequency | 50/60Hz | |||||
Frequency Range (Synchronized) | 46Hz ~ 54Hz or 56Hz ~ 64Hz | |||||
Overload Capability | 1 hour for 110%, 10 mins for 125%,; 1 min for 150%, 200ms for >150% | |||||
Harmonic Distortion | ≦ 2% THD (Linear Load) ; ≦ 4% THD (Non-linear Load) | |||||
Efficiency | Up to 92.5% at over 50% load | |||||
BATTERY / CHARGER | ||||||
Nominal Voltage | +/- 120V (12V x 20 pcs) | |||||
Float Charging Voltage | 2.3V / Cell | |||||
Boost Charging Voltage | 2.35V / Cell | |||||
Temperature Compensation | Yes | |||||
Maximum Charging Current | 8A for each power module (User-adjustable) | |||||
PHYSICAL | ||||||
Cabinet Dimension (D x W x H) mm | 1100 x 600 x 1475 | 1100 x 600 x 2010 | 1100 x 600 x 1475 | 1100 x 600 x 1475 | 1100 x 600 x 2010 | |
Net Weight (kg) | 670.5 | 926 | 329 | 428.5 | 7 Power Modules: 504 8 Power Modules: 537 | |
ENVIRONMENT | ||||||
Operating Temperature | 0 ~ 40°C | |||||
Relative Humidity | 0 ~ 95% non-condensing | |||||
Altitude | <1000m for Nominal power | |||||
IP Protection | IP 20 | |||||
MANAGEMENT | ||||||
Smart RS-232 / USB | Supports Windows® Family, Linux and MAC | |||||
Optional SNMP | Power management from SNMP manager and web browser | |||||
STANDARDS | ||||||
Safety | UL1778, CSA C22.2 No. 107.3-05 | |||||
EMC | FCC Part 15,Subpart B Class A |
* When temperature is above 30℃ , the output power factor will be de-rated, 0.9 at 31℃ ~35℃ and 0.8 at 36℃ ~40℃ .
** One battery module contains 10 pcs of 12V/7Ah or 12/9Ah sealed lead acid batteries in one tray. One complete battery set contains 4 battery modules.
*** If the UPS is installed or used in a placewhere the altitude is above than 1000m, the output power must be derated one percent per 100m.
Model | Description | Dimension DxWxH(mm) | Weight (kg) |
PM-LV20 | 3P/3P 20KVA/20KW Power Module | 736.5 x 490 x 130 (3U) | 34.5 |
Battery Module | 10 PCS of 12V 9Ah Batteries | 710 x 107 x 154 (3U) | 36 |