enquiry form:
enquiry content:

You have no items to require
Arena is applied patented modular design to enhance the flexibility of power expansion and maintenance. By simply removing four screws on the connector box, power module power can be easily removed out from cabinet without disconnecting any wires. No need for extra cabinet chassis. Compared to general parallel system, multiple Arena UPSs can form a parallel power backup system by sharing common battery packs.
Main Features |
|
|
|
|
|
|
|
|
|
|
|
|
MODEL | M33-10KL | M31-10KL | M11-10KL | M22-LV-6KL | M33-LV-10KL | |
PHASE | 3 phase in / 3 phase out | 3 phase in / 1 phase out | 1 phase in / 1 phase out | 2 phase in / 2 phase out | 3 phase in / 3 phase out | |
CAPACITY | 10000 VA / 10000 W | 10000 VA / 10000 W | 10000 VA / 10000 W | 6000 VA / 6000 W | 10000 VA / 8000 W | |
PARALLEL CAPABILITY | 10 | 10 | 10 | 10 | 10 | |
INPUT | ||||||
Nominal Voltage | 3 x 360VAC / 380VAC 400VAC / 415VAC (3Ph+N+PE) | 3 x 360VAC / 380VAC 400VAC / 415VAC (3Ph+N+PE) | 208VAC / 220VAC 230VAC / 240VAC (1Ph+N+PE) | 100VAC / 200VAC, 110VAC / 220VAC, 120VAC / 208VAC, 120VAC / 240VAC, 127VAC / 220VAC (2P+N+PE) | 3 x 173V / 190V 200V / 208V / 220V (3Ph+N+PE) | |
Voltage Range | 190-520 VAC (3-phase) @ 50% load 305-478 VAC (3-phase) @ 100% load | 110-300VAC@50% load 176-276VAC@100% load | 88-155 VAC (L-N) 152- 269 VAC (L-L) | 88-155 VAC (L-N) 152- 269 VAC (L-L) | ||
Frequency Range | 40 Hz ~ 70 Hz | |||||
Power Factor | ≧ 0.99 @ 100% load | |||||
THDi | < 4% @ full linear load | |||||
OUTPUT | ||||||
Output Voltage | 360VAC / 380VAC 400VAC / 415VAC (3Ph+N) | 208VAC* / 220VAC 230VAC / 240VAC (L+N) | 208VAC* / 220VAC 230VAC / 240VAC (L+N) | 100V / 200VAC, 110V / 220VAC, 120V / 208VAC, 120V / 240VAC, 127V / 220VAC (2P+N+PE) | 173VAC / 190VAC 200VAC (L+N) | |
AC Voltage Regulation (Batt. Mode) | ± 1% | |||||
Frequency Range (Synchronized Range) | 46~54Hz or 56~64Hz | |||||
Frequency Range (Batt. Mode) | 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz | |||||
Current Crest Ratio | 3:1 (max.) | |||||
Harmonic Distortion | ≦ 2% THD (Linear Load) ; ≦ 3% THD (Non-linear Load) | |||||
Transfer Time | AC Mode to Batt. Mode | zero | ||||
Inverter to Bypass | zero | |||||
Waveform (Batt. Mode) | Pure Sinewave | |||||
EFFICIENCY | ||||||
AC Mode | 94% | 94% | 93.5% | 91% | 92% | |
ECO Mode | 97% | 97% | 97% | 97% | 97% | |
Battery Mode | At Full Load | 93% | 92.5% | 92% | 91% | 92% |
Peak | 93.5% | 93% | 92.5% | 91.5% | 92% | |
BATTERY CHARGER | ||||||
Battery Voltage | ± 12V / 9 Ah | |||||
Battery Numbers | 16 ~ 20 pcs (adjustable) x 2 | 8~10pcs (adjustable) x 2 | ||||
Nominal Voltage | +/-192V (12V x 32 pcs) | +/-96V (12V x 16 pcs) | ||||
Maximum Voltage | +/- 240V (12V x 40 pcs) | +/-120V (12V x 20pcs) | ||||
Minimum Voltage | +/-192V (12V x 32 pcs) | +/-96V (12V x 16pcs) | ||||
Charging Voltage | ± 218V | ± 109V | ||||
Typical Recharging Time | 9 hours recover to 90% capacity | |||||
Charging Current | ± 4A | |||||
INDICATORS | ||||||
LCD/LED Display | UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions | |||||
PHYSICAL | ||||||
Dimension, D x W x H(mm) | 678 x 418 x 129 [3U] | |||||
Net Weight (kgs) | 20.5 | 20.5 | 20.5 | 17.6 | 21 | |
ENVIRONMENT | ||||||
Operating Humidity | 0-95 % RH @ 0- 40°C (non-condensing) | |||||
Noise Level | Less than 55dB @ 1 Meter | Less than 58dB @ 1 Meter | ||||
MANAGEMENT | ||||||
Smart RS-232/USB | Supports Windows® 2000/2003/XP/Vista/2008/7/8/10, Linux and MAC | |||||
Optional SNMP | Power management from SNMP manager and web browser |