Galleon T33 provides better output power factor up to 1.0 with higher performance and efficiency for critical applications. It's smae as Galleon series with programmable power management outlets which can extend available battery time to critical devices by shutting down unnecessary devies. This Galleon T33 series is also suitable for laser printer and ultrasound system load.
Main Features ( 10KVA ~ 80KVA ) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Main Features ( 100KVA ~ 200KVA ) |
|
|
|
|
|
|
|
|
|
|
MODEL | T33-10K (L)* | T33-15K(L) | T33-20K(L)* | T33-30K(L)* | T33-40K (L) | T33-60KL | T33-80KL | |
PHASE | 3-phase in / 3-phase out | |||||||
CAPACITY | 10KVA /10KW | 15KVA/15KW | 20KVA/20KW | 30KVA/30KW | 40KV /40KW | 60KVA /60KW | 80KVA/80KW | |
PARALLEL CAPABILITY | up to 6 units in parallel | |||||||
INPUT | ||||||||
Nominal Voltage | 3 x 380/400/415 VAC (3Ph+N) | |||||||
Voltage Range | -30% ~ +20% | |||||||
Frequency Range | 40~70 Hz | |||||||
Power Factor | ≧ 0.99 @ 100% Load | |||||||
Harmonic Distortion (THDi) | < 3% at full linear load | |||||||
OUTPUT | ||||||||
Output Voltage | 3 x 360*/380/400/415 VAC (3Ph+N) | |||||||
AC Voltage Regulation (Battery Mode) | ± 1% | |||||||
Frequency Range (Synchronized Range) | 46~54Hz or 56~64Hz | |||||||
Frequency Range (Battery Mode) | 50/60 Hz ± 1% | |||||||
Current Crest Ratio | 3:1 (max.) | |||||||
Harmonic Distortion | ≦ 1 % THD (Linear Load) ; ≦ 3 % THD (Non-linear Load) | |||||||
Transfer Time | AC Mode to Battery Mode | Zero | ||||||
Inverter to Bypass | Zero | |||||||
Waveform (Battery Mode) | Pure Sine wave | |||||||
Overload Capability | 100-110% for 60 min, 111-125% for 10 min, 126%~150% for 1 min; >150% or 400ms | |||||||
BYPASS | ||||||||
Nominal Voltage | 3 x 380/400/415 VAC (3Ph+N) | |||||||
Voltage Range | -30% ~ +20% (Adjustable) | |||||||
Frequency Range (Synchronized Range) | 46~54Hz or 56~64Hz | |||||||
Overload Capability | > 130% 1 minute (default), Continously working until breaker protection (optional) | |||||||
EFFICIENCY | ||||||||
AC Mode | 96.0% | |||||||
ECO Mode | 99.0% | |||||||
Battery Mode | 96.0% | |||||||
BATTERY | ||||||||
Standard Model | Battery Type | 12 V/9 Ah | 12 V/9 Ah | 12 V/9 Ah | 12 V/7 Ah | 12 V/9 Ah | N/A | |
Numbers | (10+10) pcs | (16+16) pcs | (16+16) pcs | (16+16) pcs x 2 strings | ||||
Typical Recharge Time | 9 hours recover to 90% capacity | |||||||
Charging Current (max.) | 1A ~ 12A (Adjustable) | 1A ~ 16 A (Adjustable) | ||||||
Charging Voltage | +/-136.5VDC±10% | +/-218 VDC ± 10% | ||||||
Long-run Model | Battery Type | Depending on the applications | ||||||
Numbers | +/- 10 pcs | +/-16 pcs ~ +/- 20 pcs (Adjustable) | ||||||
Charging Current (max.) | 1A ~ 12A (Adjustable) | 1A ~ 16 A (Adjustable) | 2A ~ 24 A (Adjustable) | 2A ~ 32A (Adjustable) | ||||
Charging Voltage | +/-136.5VDC±10% | +/-13.65V x N (N=16~20) | ||||||
INDICATORS | ||||||||
LCD Panel | UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions | |||||||
PHYSICAL | ||||||||
Standard Model | Dimension,DxWxH (mm) | 630 x 250 x 826 | 815 x 300 x 1000 | N/A | ||||
Net Weight (kgs) | 124 | 139 | 225 | 250 | ||||
Long-run Model | Dimension,DxWxH (mm) | 630 x 250 x 826 | 815 x 300 x 1000 | 790 x 360 x 1010 | ||||
Net Weight (kgs) | 28 | 43 | 60 | 67 | 108 | 113 | ||
ENVIRONMENT | ||||||||
Operation Temperture | 0-40°C | |||||||
Operation Humidity | < 95% and non-condersing | |||||||
Altitude** | 0 ~ 1500m at full load | |||||||
Noise Level | Less than 60 dB @1 Meter | Less than 63 dB @1 Meter | Less than 65 dB @1 Meter | |||||
MANAGEMENT | ||||||||
Smart RS-232 / USB | Supports Windows2 2000/2003/XP/Vista/2008, Windows2 7/8/10, Linux and MAC | |||||||
Optional SNMP | Power management from SNMP manager and web browser |
* If output voltage is set as 3 x 360VAC, the output power of the unit will be de-rated to 90%.
** If the UPS is installed or used in a place where the altitude is higher than maximum height, the output power will be derated 1% per 100m.
MODEL | T33-100KL | T33-120KL | T33-180KL | T33-200KL |
PHASE | 3-phase in / 3-phase out | |||
CABINET CAPACITY | 100KVA/100KW | 120KVA/120KW | 180KVA/180KW | 200KVA/200KW |
BATTERY TYPE | External Battery | |||
PARALLEL CAPABILITY | 4 | |||
INPUT | ||||
Nominal Voltage | 3 x 380/400/415 VAC (3Ph+N) | |||
Voltage Range | 110-300 VAC @ 50% load; 176-276 VAC @100% load | |||
Nominal Frequency | 50/60Hz (Auto sensing) | |||
Frequency Range | 40Hz ~70Hz | |||
Power Factor | ≧ 0.99 @ 100% load | |||
Harmonic Distortion (THDi) | < 4% at full linear load | |||
OUTPUT | ||||
Nominal Voltage | 3 x 380/400/415 VAC (3Ph+N) | |||
Voltage Regulation (Steady state) | ≦ ± 1% Typical (balanced load) ≦ ± 2% Typical (unbalanced load) | |||
Nominal Frequency | 50/60Hz | |||
Frequency Range (Synchronized range) | 46Hz ~ 54Hz or 56Hz ~ 64Hz | |||
Overload Capability | ≦ 110% for 1 hour, 111% ~ 125% for 10 mins, 126%~150% for 1 min and >150% for 200ms | |||
Harmonic Distortion | ≦ 2% THD (Linear Load) ; ≦ 4% THD (Non-linear Load) | |||
EFFICIENCY | ||||
AC Mode | 95.5% | |||
ECO Mode | 98.5% | |||
Battery Mode | 94.5% | |||
BYPASS | ||||
Nominal Voltage | 3 x 380/400/415 VAC (3Ph+N) | |||
Voltage Range | -30% ~ +20% | |||
Frequency Range | 46Hz ~ 54Hz or 56Hz ~ 64Hz | |||
Overload Capability | ≦ 110% for 1 hour, 111% ~ 125% for 10 mins, 126%~150% for 1 min and >150% for 200ms | |||
BATTERY / CHARGER | ||||
Nominal Voltage | +/- 192V ~ +/- 240V (Selectable) | |||
Maximum Voltage | +/- 240V (12V x 40 Pcs) | |||
Minimum Voltage | +/- 192V (12V x 32 Pcs) | |||
Floating Charge Voltage | 2.28V / Cell (2.25 ~2.33 Selectable) | |||
Boost Charging Voltage | 2.35V/Cell | |||
Temperature Compensation | Yes | |||
Maximum Charging Current (Per Power Module) | 24A (Adjustable) | 36A (Adjustable) | 54A (Adjustable) | 54A (Adjustable) |
PHYSICAL | ||||
IP Class | IP20 | |||
Dimension, D x W x H (mm) | 1000 x 430 x 1200 | 1000 x 430 x 1200 | 1000 x 600 x 1200 | 1000 x 600 x 1200 |
Net Weight (Kgs) | 200 | 200 | 265 | 265 |
ENVIRONMENT | ||||
Operating Temperature | 0-40°C | |||
Operating Humidity | < 95 % and non-condensing | |||
Altitude** | <1000m for Nominal power | |||
MANAGEMENT | ||||
Smart RS-232/USB | Supports Windows® Family, Linux and MAC | |||
Optional SNMP | Power management from SNMP manager and web browser | |||
STANDARDS | ||||
Safety | IEC/EN 62040-1 | |||
EMC | IEC/EN 62040-2 Category C3 |