Ideal for medium-density power protection demand, Galleon X9 series provides Rack/Tower form factor to fit diverse environment. Despite its compact footprint, this UPS incorporates internal battery packs which can be accessed via the front panel for maintenance checks and replacement without removing the UPS from its rack mounting. The LCD display panel can be essily shifted by pressing buttons to suit the installation format, vertically stand or flatly rack mount. Besides, IT personel can manag
Main Features ( 1KVA / 2KVA / 3KVA ) |
|
|
|
|
|
|
|
|
|
Main Features ( 6KVA / 10KVA ) |
|
|
|
|
|
|
|
|
|
|
|
MODEL | Galleon X9 1K (L) | Galleon X9 1.5K (L) | Galleon X9 2K (L) | Galleon X9 3K (L) | ||||
PHASE | Single phase with ground | |||||||
CAPACITY | VA/W | 1000 VA / 900W | 1500 VA / 1350W | 2000 VA / 1800W | 3000 VA / 2700W | |||
INPUT | ||||||||
Nominal Voltage | 100*/110*/115*/120 /127 VAC or 200/208/220/230/240 VAC | |||||||
Voltage Range | 55-150 VAC ± 5% or 110-300 VAC ± 5% @ 50% load ; 80-150 VAC ± 5% or 160-300 VAC ± 5% @ 100% load | |||||||
Frequency Range | 40Hz ~ 70Hz | |||||||
Harmonic Distortion(THDi) | ≦ 5% @ nominal input voltage | |||||||
Power Factor | ≧ 0.99 @ Nominal Voltage (100% Load) | |||||||
OUTPUT | ||||||||
Output Voltage | 100*/110*/115*/120/127 VAC or 200/208/220/230/240 VAC | |||||||
AC Voltage Regulation (Battery Mode) | ± 1% | |||||||
Frequency Range (Synchronized Range) | 57 ~ 63 Hz or 47 ~ 53 Hz | |||||||
Frequency Range (Battery Mode) | 60Hz ± 0.1Hz or 50 Hz ± 0.1Hz | |||||||
Current Crest Ratio | 3:1 (max.) | |||||||
Harmonic Distortion | ≦ 2 % THD (Linear Load) ; ≦ 4 % THD (Non-linear load) | |||||||
Transfer Time | AC Mode to Battery Mode | Zero | ||||||
Inverter to Bypass | 4 ms (Typical) | |||||||
Waveform (Battery Mode) | Pure Sinewave | |||||||
EFFICIENCY | ||||||||
AC Mode | 90% | 90% | 91% | 91% | ||||
ECO Mode | 97% | 97% | 97% | 97% | ||||
Battery Mode | 88% | 89% | 89% | 88% | 89% | 80% | ||
BATTERY | ||||||||
Stanard Model | Battery Type | 12 V / 9 Ah | 12 V / 7 Ah | 12 V / 9 Ah | 12 V / 9 Ah | 12 V / 7 Ah | 12 V / 9 Ah | |
Numbers | 2 | 3 | 3 | 4 | 6 | 6 | ||
Typical Recharge Time | 4 hours recover to 90% capacity | |||||||
Charging Current (max.) | 1.5 A* | |||||||
Charging Voltage | 27.4 VDC ± 1% | 41.1 VDC ± 1% | 41.1 VDC ± 1% | 54.8 VDC ±1% | 82.1 VDC ±1% | 82.1 VDC ±1% | ||
Long-run Model | Battery Type | Depending on the capacity of external batteries | ||||||
Numbers | 2 | 3 | 3 | 4 | 6 | 6 | ||
Charging Current (max.) | 1A / 2A / 4A / 8A | |||||||
Charging Voltage | 27.4 VDC ± 1% | 41.1 VDC ± 1% | 41.1 VDC ± 1% | 54.8 VDC ±1% | 82.1 VDC ±1% | 82.1 VDC ±1% | ||
INDICATORS | ||||||||
LCD Display | Load level, Battery level, AC mode, Battery mode, Bypass mode, and Fault indicator | |||||||
ALARM | ||||||||
Battery Mode | Sounding every 4 seconds | |||||||
Low Battery | Sounding every second | |||||||
Overload | Sounding twice every second | |||||||
Fault | Continously sounding | |||||||
PHYSICAL | ||||||||
Stanard Model | Dimension, DxWxH (mm) | 410 x 438 x 88 [2U] | 410 x 438 x 88 [2U] | 510 x 438 x 88 [2U] | 630 x 438 x 88 [2U] | 630 x 438 x 88 [2U] | ||
Net Weight (kgs) | 11.6 | 14.2 | 14.5 | 19.5 | 26.5 | 27.4 | 10.5 | |
Long-run Model | Dimension, DxWxH (mm) | 410 x 438 x 88 [2U] | 410 x 438 x 88 [2U] | 410 x 438 x 88 [2U] | 510 x 438 x 88 [2U] | |||
Net Weight (kgs) | 6.5 | 6.5 | 6.5 | 10.5 | ||||
ENVIRONMENT | ||||||||
Humidity | 20-90 % RH @ 0- 40°C (Non-condensing) | |||||||
Noise Level | Less than 50dBA @ 1 Meter | |||||||
MANAGEMENT | ||||||||
Smart RS-232 / USB | Supports Windows2 2000/2003/XP/Vista/2008, Windows2 7/8/10, Linux, Unix, and MAC | |||||||
Optional SNMP | Power management from SNMP manager and web browser |
MODEL | Galleon X9 6K(L) | Galleon X9 ISO 6K(L) | Galleon X9 10K(L) | Galleon X9 ISO 10K(L) | |
PHASE | Single phase with ground | ||||
CAPACITY | 6000 VA / 5400 W | 10000 VA / 9000 W | |||
INPUT | |||||
Nominal Voltage | 200/208/220/230/240 VAC | ||||
Voltage Range | 110-300 VAC ± 3% at 50% load ; 176-300 VAC ± 3% at 100% load | ||||
Frequency Range | 46~54 Hz or 56~64 Hz | ||||
Power Factor | ≧ 0.99 @ 100% load | ||||
OUTPUT | |||||
Nominal Voltage | 200/208/220/230/240 VAC | 104 VAC x 2 / 208 VAC or 110 VACx 2 / 220 VAC or 115 VAC x 2 /230 VAC or 120 VAC x 2 / 240 VAC | 200/208/220/230/240 VAC | 104 VAC x 2 / 208 VAC or 110 VACx 2 / 220 VAC or 115 VAC x 2 /230 VAC or 120 VAC x 2 / 240 VAC | |
AC Voltage Regulation | ± 1% | ± 3% | ± 1% | ± 3% | |
Frequency Range(Synchronized Range) | 46~54 Hz or 56~64 Hz | ||||
Frequency Range(Battery Mode) | 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz | ||||
Current Crest Ratio | 3:1 (max.) | ||||
Harmonic Distortion | ≦ 2 % THD (Linear Load), ≦ 4 % THD (Non-linear Load) | ≦ 3.5 % THD (Linear Load), ≦ 7 % THD (Non-linear Load) | ≦ 2 % THD (Linear Load), ≦ 4 % THD (Non-linear Load) | ≦ 3.5 % THD (Linear Load), ≦ 7 % THD (Non-linear Load) | |
Transfer Time | AC Mode to Battery Mode | Zero | |||
Inverter to Bypass | Zero | ||||
Waveform (Battery Mode) | Pure Sinewave | ||||
EFFICIENCY | |||||
AC Mode | 91% | 85% | 91% | 85% | |
ECO Mode | 96% | 87% | 96% | 87% | |
Battery Mode | 88% | 82% | 88% | 82% | |
BATTERY | |||||
Standard Model | Battery Type | 12 V / 7 Ah | 12 V / 9 Ah | ||
Numbers | 20 (18-20 pcs adjustable)* | 20 (18-20 pcs adjustable)* | |||
Typical Recharge Time | 7 hours recover to 90% capacity | 9 hours recover to 90% capacity | |||
Charging Current (max.) | 1.0 A | 1.0 A | |||
Float Charging Voltage | 273 VDC (based on battery numbers at 20 pcs) | ||||
Long Run Model | Battery Type and Numbers | Depending on applications | |||
Charging Current (max.) | 4.0 A | 4.0 A | |||
Float Charging Voltage | 273 VDC (based on battery numbers at 20 pcs) | ||||
INDICATORS | |||||
LCD Display | UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions | ||||
ALARM | |||||
Battery Mode | Sounding every 4 seconds | ||||
Low Battery | Sounding every second | ||||
Overload | Sounding twice every second | ||||
Fault | Continously sounding | ||||
PHYSICAL | |||||
Standard Model | Dimension, D x W x H (mm) | UPS unit: 606 x 438 x 133 [3U] Battery pack: 606 x 438 x 133 [3U] | UPS unit: 606 x 438 x 133 [3U] Battery pack: 606 x 438 x 133 [3U] ISO bank: 606 x 438 x 133 [3U] | UPS unit: 686 x 438 x 133 [3U] Battery pack: 606 x 438 x 133 [3U] | UPS unit: 686 x 438 x 133 [3U] Battery pack: 606 x 438 x 133 [3U] ISO bank: 686 x 438 x 133 [3U] |
Net Weight (kgs) | UPS unit: 20 Battery pack: 58 | UPS unit: 20 Battery pack: 58 / ISO bank: 61 | UPS unit: 23.5 Battery pack: 65 | UPS unit: 23.5 Battery pack: 65 / ISO bank: 90 | |
long-run Model | Dimension, D x W x H (mm) | 606 x 438 x 133 [3U] | UPS unit: 606 x 438 x 133 [3U] ISO bank: 606 x 438 x 133 [3U] | 686 x 438 x 133 [3U] | UPS unit: 686 x 438 x 133 [3U] ISO bank: 686 x 438 x 133 [3U] |
Net Weight (kgs) | 20 | UPS unit: 20 / ISO bank: 61 | 23.5 | UPS unit: 23.5 / ISO bank: 90 | |
ENVIRONMENT | |||||
Operating Humidity | 0-95 % RH @ 0- 40°C (Non-condensing) | ||||
Noise Level | Less than 58dB @ 1 Meter | Less than 60dB @ 1 Meter | |||
MANAGEMENT | |||||
Smart RS-232 / USB | Supports Windows2 2000/2003/XP/Vista/2008, Windows2 7/8/10, Linux and MAC | ||||
Optional SNMP | Power management from SNMP manager and web browser |